Product data sheet
Valve
A3525-0804-R322-TM-1U-2,
October 24, 2026
Seat Valve electrically force-controlled
Series 35-08-TH
Valve A3525/0804/.322-TM-1U-2 AC, DC
The solenoid valve Type 35-TH is used for high temperatures of up to + 180 °C. It can be supplied either in brass or stainless steel and is suitable for hot water and steam applications in the plant and mechanical engineering field. The standard valve is non energized closed - NC. A non energized open -NO design can also be supplied. Temperatureresisting limit switches for both positions, i.e. OPEN and CLOSED can be added on request.
For more information follow this link:
Valve A3525/0804/.322-TM-1U-2 AC, DC
Datasheet explicit
Instructions
Instructions Solenoid valves, forced-operated
Stroke setting G2/DN50 Type 35/37-272/278
SIL2 Overview DN15-25, NC
Solenoid coil R322
Others
Turck BIM-PST-AP6X_46240
Sensor cable M8 3-wire 2m
Service card sensor, setting instructions
EC Declaration of Conformity
REACH Declaration
RoHS Declaration
Videos
| Version | A | |
| Type of valve | 35 | Seat Valve electrically force-controlled |
| Connection type, valve seat | 25 | G1 25mm |
| Kv-value (Δp = 1 bar H₂O) | 12 m³/h | |
| Housing | 08 | AISI 316 Ti |
| Sealing | 04 | PTFE |
| Voltage type | -- | To be specified later |
| Solenoid power | 32 | 21W |
| Protection class | 2 | IP65 (STD) |
| Valve option | TM-1U-2 | normally closed + Temperature design + Magnetic switch 1-fold CLOSE induc. 3-wire N/O contact PNP |
| Pressure rating | PN40 | |
| System pressure | 0 - 25 bar | |
| Valve type | 12V, 24V, 48V, 110V, 120V, 220V, 230V, AC, DC | |
| Temperature Medium | from -20 °C to 180 °C | |
| Temperature Environment | from -40 °C to 40 °C | |
| Mounting position | Actuator upright (preferred) or horizontal | |
| Specific use case | Closed system (includes open system) | |
| scope of delivery | 1 valve, 1 Connector w. rectifier & VDR EN 175301-803 A | IP65 when installed | Connectable cables Ø 4.5-11mm max.1.5mm² | 1 Solenoid Steel R322 | rotatable 360° | Valve MatchCode G0xx.xxxxxx.0xx.002.0xx | 1 connector FormA EN175301-803/A | max. current 10A | 4x90°| IP65 when installed | connectable cables Ø 5-10 mm max.1.5mm² | Valve MatchCode G0xx.xxxxxx.0xx.009.0xx | |
| Valve option | TM-1U-2 | normally closed + Temperature design + Magnetic switch 1-fold CLOSE induc. 3-wire N/O contact PNP |
| Description | Valve closed when de‑energized | Magnetic field sensor | Turck BIM-PST-AP6X_46240 | place of install.: top | Signal: closed | |
| Leakage rate | B - EN 12266-1 [Test medium air or nitrogen, 20°C room temperature] | |
| REACH-RoHS conformity | REACH Yes | RoHS Yes | |
| Net weight | 3.1 kg | |
| Switching time (at 6 bar gas) | On: 120 ms | Off: 160 ms | |
| Customs export | Customs tariff number 84818073; Country of origin Germany; ECCN (US): N; AL: N |